Kohler 48RCLC Specifications

Specification Kohler 48RCLC
LP / natural-gas output 48 / 48 kW
Motor-starting rating 113 kVA peak; not continuous kW
Engine KG6208, 6.2L V8
Cooling / engine speed Liquid-cooled / 1,800 rpm
Starting MSRP $25,703; equipment only
Weight 1,690 lb
Starting battery Group 24, 12V, minimum 630 CCA
NG at half / full load 512 / 875 ft³/hr
LP vapor at half / full load 165 / 315 ft³/hr
Catalog sound: exercise / operation 57 / 61 dBA; see measurement caveat
Controller RDC2
Application Utility backup

Scope: U.S. 120/240V single-phase, 60Hz configuration. MSRP and catalog sound figures checked September 30, 2026. Fuel figures follow the linked April 2026 technical sheet.

Source: Kohler 48RCLC technical specification.

Source: Kohler 48RCLC consumer catalog.

Where the 48RCLC Fits

The Kohler 48RCLC is intended for large simultaneous loads where the 38RCLC is insufficient, with a 6.2L V8 and substantial installation footprint. On natural gas, plan against 48kW rather than the propane nameplate. The 113kVA starting rating describes a short motor-start event and cannot be added to the running output.

Inventory the loads you need during an outage, including HVAC starting current, pumps and electric heat. Use the generator size calculator to organize the load list, then have an installer check the design against the exact alternator and fuel configuration.

Equipment Cost and Installation Scope

Kohler’s starting equipment MSRP for the 48RCLC is $25,703, checked September 30, 2026. That is not an installed price.

A complete quote should itemize the generator, compatible transfer switch, battery, foundation, electrical and fuel work, permits, commissioning, registration and any load controls or cold-weather accessories. Long trenching runs, gas-meter upgrades and changes to service panels can materially change the total. Compare equivalent scopes from local installers; no national installed average is asserted here.

Source: Kohler 48RCLC consumer catalog.

Transfer Switch and Fuel Supply

Budget and specify the automatic transfer switch separately unless the seller explicitly includes a compatible unit in the quoted package. Match switch amperage, service-entrance suitability, number of panels and load management to the installation design. A generator’s kW rating alone does not determine the correct transfer switch.

Source: Kohler 48RCLC technical specification.

At full load, the technical sheet lists 875 ft³/hr of natural gas and 315 ft³/hr of LP vapor. Have the installer check fuel supply with the other connected appliances operating; a meter label or short pipe run alone does not establish sufficient capacity.

Ownership and Service

TP-7102 lists oil and filter changes yearly or at 150 operating hours. Check oil every 24 hours or before each day’s operation. Use the complete current manual for air-filter, ignition, battery and other service tasks. Severe conditions may require shorter intervals; match the manual to your model and serial number.

Source: Kohler 48RCLC operation manual.

Compare the Kohler Line

Compare running output on your actual fuel, peak motor starting, cooling architecture and installed system cost. Local commissioning, parts access and service response are material parts of the purchase.